[The Super Blog ](https://www.superradiatorcoils.com/blog)

# [R-448A: Pros, Cons, & Comparisons to Other Refrigerants | Super Radiator Coils](https://www.superradiatorcoils.com/blog/r-448a-pros-cons-performance-comparisons)

 Written by [Super Radiator Coils](https://www.superradiatorcoils.com/blog/author/super-radiator-coils) | Oct 14, 2022 12:41:47 PM

Our refrigerant focus series consists of deep dives into the history, properties, suitable applications and pros and cons of some of today’s common refrigerants. This installment will focus on R-448A.

- [Refrigerant Focus #1: R-32](https://www.superradiatorcoils.com/blog/refrigerant-focus-r-32-difluoromethane)
- [Refrigerant Focus #2: R-410A](https://www.superradiatorcoils.com/blog/refrigerant-focus-r-410a)
- [Refrigerant Focus #3: R-1234ze](https://www.superradiatorcoils.com/blog/r-1234ze-pros-cons-comparisons)
- [Refrigerant Focus #4: R-407A](https://www.superradiatorcoils.com/blog/r-407a-pros-cons-comparisons-r-404a-r-22)
- [Refrigerant Focus #5: R-290](https://www.superradiatorcoils.com/blog/r-290-pros-cons-comparisons-r22-r134a-r404a)
- [Refrigerant Focus #6: R-744 (CO2)](https://www.superradiatorcoils.com/blog/co2-pros-cons-comparisons)
- [Refrigerant Focus #8: R-454B](https://www.superradiatorcoils.com/blog/r-454b-pros-cons-comparisons-to-r-410a)

## History of R-448A as a Refrigerant

R-448A was developed between 2010 and 2015, the result of a collaborative effort among Honeywell, the University of Maryland, and Oak Ridge National Laboratory’s Building Technologies Research & Integration Center.

[The stated goal of this research](https://www.energy.gov/eere/buildings/articles/low-gwp-refrigerants-refrigeration-systems) was to develop next-gen refrigerants, the performance of which would allow for a 50% reduction in energy consumption of the equipment in which it was used. Specifically, this work sought to synthesize a refrigerant to replace R-22, R-404A, and R-507 in low-to-medium temperature applications, such as supermarket refrigeration.

## Properties of R-448A

R-448A is a low-toxicity, non-flammable blended refrigerant, classified by ASHRAE into safety group A1. It's is a 5-part zeotropic blend, made using a combination of hydrofluorocarbon and hydrofluoroolefin constituents at the concentrations outlined below.

- R-32 (26%)
- R-125 (26%)
- R-134a (21%)
- R-1234ze (7%)
- R-1234yf (20%)

The table below shows R-448A’s properties compared to the properties of the refrigerants it is intended to replace.

| ** ** | **R-448A** | **R-404A** | **R-22** |
| --- | --- | --- | --- |
| **Formula** | R-32 (26%) R-125 (26%) R-134a (21%) R-1234ze (7%) R-1234yf (20%) | R-125 (44%) R-143A (52%) R-134A (4%) | CHCLF2 |
| **Molecular weight (g/mol)** | 86.3 | 97.6 | 86.47 |
| **Boiling Temp ˚F (˚C)** | -43.27 (-45.9) | -51 (-46.2) | -41.4 (-40.8) |
| **Critical Temp ˚F (˚C)** | 182.6 (83.7) | 161.7 (72) | 205 (96.1) |
| **Critical pressure, PSI (Bar)** | 675.9 (46.6) | 541 (37.7) | 723.7 (49.9) |
| **Global Warming Potential** | ~1360 | 3922 | ~1810 |
| **Ozone Depletion Percentage** | 0 | 0 | 0.05 |
| **ASHRAE Safety Group** | A1 | A1 | A1 |

 

## Performance Comparison of R-448A vs. R-404 & R-22

For a performance comparison, we’ve run a theoretical 6” x 70” 8-row copper-aluminum [evaporator](https://www.superradiatorcoils.com/products/coils/condenser-coils) through our coil selection software, [Enterprise](https://apps.superradiatorcoils.com/). The coil’s [airside](https://www.superradiatorcoils.com/research-and-development/wind-tunnel-test-lab) and [tube-side](https://www.superradiatorcoils.com/research-and-development/tube-side-refrigerant-lab) requirements are below and the [coil’s](https://www.superradiatorcoils.com/products/coils) rating is below that. 

| **Inputs** |  |  |  |
| --- | --- | --- | --- |
| **Airside** | **Tube-side** |  |  |
| **Airflow** | 4,000 SCFM | **Refrigerant suction temp** | 35 ˚F |
| **Target capacity** | 140,000 Btu/Hr. | **Degrees superheat** | 6 ˚F |
| **Entering air temp (dry bulb)** | 85 ˚F | **Liquid temp** | 100 ˚F |
| **Leaving air temp (dry blub)** | 55 ˚F |   |   |
| **Air pressure** | 14.696 PSIA |   |   |

 

| **Performance Comparison: R-448A vs. R-404A** |  |  |  |  |
| --- | --- | --- | --- | --- |
|   | **R-448A** | **R-404A** | **Difference (%)** | **Difference (abs.)** |
| **Coil capacity** | 145,558 Btu/hr. | 140,680 Btu/hr. | 3.3% | 4,878 Btu/hr. |
| **Leaving air temp.** | 51.6°F | 52.7°F | -2.6% | 1.1°F |
| **Refrigerant inlet temperature** | 33.7°F | 42.7°F | -27% | 9°F |
| **Refrigerant pressure drop** | 7.694 PSI/coil | 13.419 PSI/coil | -74% | 5.725 PSI/coil |
| **Refrigerant mass flow** | 2,179 lb./hr. | 3,228 lb./hr. | -48% | 1,049 lb./hr. |
| **Circuit loading** | 12,130 Btu/hr. | 11,723 Btu/hr. | 3.3% | 407 Btu/hr. |

 

| **Performance Comparison: R-448A vs. R-22** |  |  |  |  |
| --- | --- | --- | --- | --- |
|   | **R-448A** | **R-22** | **Difference (%)** | **Difference (abs.)** |
| **Coil capacity** | 145,558 Btu/hr. | 144,347 Btu/hr. | 0.8% | 1,211 Btu/hr. |
| **Leaving air temp.** | 51.6°F | 51.9°F | 0.6% | 0.3°F |
| **Refrigerant inlet temperature** | 33.7°F | 40.1°F | 19% | 6.4°F |
| **Refrigerant pressure drop** | 7.694 PSI/coil | 6.905 PSI/coil | -10.2% | 0.789 PSI/coil |
| **Refrigerant mass flow** | 2,179 lb./hr. | 2,082 lb./hr. | -4.4% | 97 lb./hr. |
| **Circuit loading** | 12,130 Btu/hr. | 12,029 Btu/hr. | -0.8% | 101 Btu/hr. |

 

## Pros & Cons of R-448A

### R-448A: Pros

The chief benefit of R-448A is its lessened environmental impact relative to the refrigerants it was designed to replace. It’s non-ozone depleting and has a global warming potential of 1320, which is 37% less than R-22 and 197% less than R-404.

And, while R-448A’s performance compares similarly to R-22, that refrigerant has been nearly totally phased out. And when compared to the less-regulated R-404A, R-448A resulted in a per-coil capacity increase of just over 3%. R-448A also demonstrated a significantly lower (74%) pressure drop in our hypothetical application.

### R-448A: Cons

One minor drawback of R-448A is that, due to it being a zeotropic mixture, it does have a temperature glide of between 5 and 8˚F – a variable that merits attention when designing equipment.

*Don’t get left out in the cold when it comes to heat transfer information. To stay up to date on a variety of topics on the subject, [subscribe to The Super Blog](https://www.superradiatorcoils.com/blog-subscribe), our technical blog, [Doctor's Orders](https://www.superradiatorcoils.com/blog-subscribe-doctors-orders), and follow us on [LinkedIn,](https://www.linkedin.com/company/super-radiator-coils/?viewAsMember=true) [Twitter,](https://twitter.com/SuperRadiator) and [YouTube.](https://www.youtube.com/user/SuperRadiatorCoils)*

[View full post](https://www.superradiatorcoils.com/blog/r-448a-pros-cons-performance-comparisons)

```json
{
  "@context" : "http://schema.org",
  "@type" : "BlogPosting",
  "author" : {
    "@type" : "Person",
    "name" : "Super Radiator Coils"
  },
  "dateModified" : "2024-05-02T16:42:13.442Z",
  "datePublished" : "2022-10-14T12:41:47Z",
  "headline" : "R-448A: Pros, Cons, & Comparisons to Other Refrigerants",
  "image" : {
    "@type" : "ImageObject",
    "height" : 2918,
    "url" : "https://6657658.fs1.hubspotusercontent-na1.net/hubfs/6657658/r448a-refrigerant%20focus-7-min.png",
    "width" : 3334
  },
  "mainEntityOfPage" : "https://www.superradiatorcoils.com/blog/r-448a-pros-cons-performance-comparisons",
  "publisher" : {
    "@type" : "Organization",
    "logo" : {
      "@type" : "ImageObject",
      "height" : 60.0,
      "url" : "https://f.hubspotusercontent00.net/hubfs/6657658/SRC_April20/Home/logo.png",
      "width" : 238.481
    },
    "name" : "The Super Blog"
  }
}
```